EloStar Master 3X0 / 4X0 / - smart
System Description
Manual V.1.03H
19
UIS (Universal Interlocking System) Functions
User related access counter CIT
Setting of number of openings that CIT u
sers can carry out during the “time frame” (see
below) set for them.
Range of values: 00-99, default value: 00 openings (option switched off).
User related time frame after first opening CIT [min]
Setting of number of minutes during which the CIT users can carry out the number of
openings specified via field “…access counter CIT” (see above). Enter value “00” in order
to switch the function off.
Range of values: 00-99 minutes, default value: 00 minutes (option switched off).
No-return functionality
(optional)
Mark this box in order to activate the no-
return functionality in general. Also see box ’no-
return code
’ of the user matrix. Via this box you can assign no-return code to individual
users with which the users can open once within a set time frame. Once they have
opened, individual users cannot carry out further openings until another user has opened
the lock in the meantime.
Extension of ‚Customer data‘
The fields ‚Serial number‘, ‚Type of safe‘, ‚Object number‘ and ‚Inventory number‘ have
b
een added to tab ‚Customer data‘. Additional data can be processed via these fields.
The fields can be used for optional additional security features, for example.
3.3.4
Optional Functions with Version EM12 and higher
This firmware version is compatible to FlatControl only. If not marked otherwise, the
functions are available also for systems with QPad. The version of the firmware can be
displayed via menu
Status / Info
. See page 92. Some of these functions can be
programmed with the optional configuration software PC-Software QPadComm /
TwinComm.
User numbers can be entered temporarily instead of personnel numbers for
the registration and deregistration of code cards
During the registration and the deregistration of code cards you will be asked whether
personnel numbers are to be used.
Select „NO“, if required, and „User numbers“ in order
to register and deregister code cards. With FlatControl only.
„Personnel number not identified“ is displayed after an invalid personnel
number has been entered.
„Personnel number not identified“ is displayed as error message instead of „invalid card“
displayed previously when a wrong personnel number has been entered.
Language cards can be read with the system closed
Not evaluated by UL.
With the option „Configuration in a closed system“ selected,
language cards can be read with the system closed.
Via TwinComm you can set that the door switch / bolt work contact is
connected directly at the lock, not via extension unit
In section “Settings | Closing” can set that the door switch / bolt work contact is
connected directly at the lock, not via extension unit (via field “Door switch on lock”).