Chapter 5 Parameter Description
- 65 -
Parameter
No.
Parameter Name
Setting Range
Default
Unit
Property
F0-05
Door open timeout
30–1000
60
s
☆
If the door open time of an elevator is longer than the value set in F0-05, the system
determines that a door open timeout occurs (because the light curtain is blocked or the
door open button is held down for a long time). Then, the system assigns a call to other
elevators first.
Parameter
No.
Parameter Name
Setting Range
Default
Unit
Property
F0-06
Parking time
0–10
2
min
☆
When the group control system detects that the idle time of an elevator exceeds the
value set in F0-06, it assigns the elevator to implement dispersed parking.
Parameter
No.
Parameter Name
Setting Range
Default
Unit
Property
F0-07
Parking floor 1
0–56
0
-
☆
F0-08
Number of elevators
on parking floor 1
1–8
1
-
☆
F0-09
Parking floor 2
0–56
0
-
☆
F0-10
Number of elevators
on parking floor 2
1–8
1
-
☆
F0-11
Parking floor 3
0–56
0
-
☆
F0-12
Number of elevators
on parking floor 3
1–8
1
-
☆
The parameters F0-07 and F0-08, F0-09 and F0-10, and F0-11 and F0-12 work together in
pairs. When the system implements dispersed parking, it assigns a specified number of
idle elevators to each parking floor.
To enable this function, set Bit0 of F4-11 to 0.
Parameter
No.
Parameter Name
Setting Range
Default
Unit
Property
F0-13
VIP floor 1
0–56
0
-
☆
F0-14
VIP floor 2
0–56
0
-
☆
If a floor is set as a VIP floor, calls from this floor are VIP calls. If an elevator responds to
a VIP call, the system does not assign this elevator to respond to other calls.
Parameter
No.
Parameter Name
Setting Range
Default
Unit
Property
F0-15
Maximum number
of elevators that can
be powered by the
backup power supply
Maximum number
of
operational
elevators when
the backup power
supply is used:
0–65535
1
-
☆