Chapter 3 System Commissioning
- 36 -
F0
F0-00
1
Level I menu
Level II menu
Level III menu
Return
Abort
Save
F0-02
Enter
Return
Next parameter No.
(
Set the parameter value)
(
Select the parameter No.)
(
Select the parameter group)
If there is a blinking digit, press ,
or to modify the digit.
PRG
PRG
PRG
ENTER
ENTER
ENTER
Enter
Enter
ENTER
Figure 3-2 Operation flowchart of the three-level menu
Note:
You can return to Level II menu from Level III menu by pressing
PRG
or
ENTER
.
The difference between the two is as follows:
After you press
ENTER
, the system saves the parameter setting, goes back to Level II
menu and automatically shifts to the next parameter.
After you press
PRG
, the system does not save the parameter setting, but directly goes
back to Level II menu and remains at the current parameter.
Example:
Change the value of F2-00 from
0
to100.
F0
F1
F2
F2-01
100
000
F2-00
000
F2
ENTER
ENTER
ENTER
PRG
In Level III menu, if a parameter has no blinking digit, it indicates that the parameter
cannot be modified. This may be because such a parameter is only readable, such as an
actually-detected parameter or version display parameter.
3 Password Setting
The GCB provides a password protection function. When FP-00 (
User password
) is set
to a non-zero value, it is a user password. The password takes effect after you exit the
parameter editing state. After you press
PRG
, "-----" is displayed. You must enter the
correct user password to enter level I menu.
To cancel the password protection function, enter the menu with correct password and
then set FP-00 (
User password
) to 0. If FP-00 (
User password
) is a non-zero value upon
power-on, the parameters are protected by a password.