88-A951X001-1D-EN
95
Integrated Furnace Control Menu
IdL
STATUS MENU
Err
ACTIVE ERRORS
Ht
tp5
Example
Gas Heat
Example
Tap 5
E3.1
Example
Pressure Switch Error
L6F
LAST 6 FAULTS
E3.1
E04
Example
Pressure Switch Error
Example
Open Limit Switch Error
CR1
Control Release #
CR
Example
Software Version #
COd
Cooing Off Delay
000
090
180
Example
seconds
ODU
Outdoor Stages
1-1
HOD
Heat Off Delay
100
060
Example
seconds
COF
Continuous Fan Tap
CF.1
Example
Tap #
COP
Compressor Operation
Speed Tap
Example
Tap #
Example
Gas Heat Tap #
A951X
Control System Menu Single Stage OD
140
CLEARING THE LAST6 FAULTS:
To clear the stored faults, scroll to the last 6 faults
menu, enter the menu by scrolling to the right and hold
the “Option” key for at least 5 seconds. Release and a
set of 3 dashes will be seen 3 times. This confirms the
faults have been cleared
SETTING UP YOUR SYSTEM:
To change any factory default value, first remove any
“call” from the furnace and allow all fan off delays to
finish. (
IDL
should be seen on the display)
Scroll to the selected Menu item by momentarily
depressing the “MENU” key and then depress the
“OPTION” key to the desired setting. Then momentarily
depress the “MENU” key again to save the change.
180
C1.7
C1.8
C1.9
C1.1
C1.2
HtP
Heating Speed Tap
H1.5
H1.6
01
H1.7
H1.8
Example
Single Stage
SELECTING GAS HEAT FAN SPEEDS:
Airflow can be adjusted while the unit is running.
Scroll to the
HTP
menu and momentarily push the OPTION key. Tap #5 is the
default setting for all models. When selection is made, momentarily push the
MENU key to save.
If the temperature rise is too high, increase airflow. If the temperature rise too
low, decrease airflow.
NOTE:
Tap 9 is not available for gas heating
run
Run Test Mode
Designated Gas Heating Airflow Taps
Upflow
A951X040BU3SAB (1-6)
A951X060BU4SAB (1-7)
A951X080BU4SAB (1-7)
A951X080CU5SAB (1-7)
A951X100CU5SAB (1-7)
A951X120DU5SAB (1-7)
Downflow
A951X040BD3SAB (1-6)
A951X060BD3SAB (1-7)
A951X080BD4SAB (1-6)
A951X100CD5SAB (1-7)
A951X120DD5SAB (1-7)
SELECTING COOLING/HP FAN SPEEDS for 1-1 ODU:
Airflow can be adjusted while the unit is running.
Scroll to the
COP
menu and momentarily push the OPTION key. Tap 7 is the
default setting for all models. When selection is made, momentarily push the
MENU key to save.
ORN
LED Orientation
Not Applicable
UP
Dn
C1.3
C1.4
C1.5
C1.6
H1.1
H1.2
H1.3
H1.4
Continuous Fan
Do Not Adjust Above Tap 1
Содержание A951X040BD3SAB
Страница 13: ...88 A951X001 1D EN 13 Outline Drawings Upflow Furnace B Size Cabinet ...
Страница 14: ...14 88 A951X001 1D EN Upflow Furnace C Size Cabinet O Ou ut tl li in ne e D Dr ra aw wi in ng gs s ...
Страница 15: ...88 A951X001 1D EN 15 Upflow Furnace D Size Cabinet O Ou ut tl li in ne e D Dr ra aw wi in ng gs s ...
Страница 16: ...16 88 A951X001 1D EN Downflow Furnace B Size Cabinet O Ou ut tl li in ne e D Dr ra aw wi in ng gs s ...
Страница 17: ...88 A951X001 1D EN 17 Downflow Furnace C Size Cabinet O Ou ut tl li in ne e D Dr ra aw wi in ng gs s ...
Страница 18: ...18 88 A951X001 1D EN Downflow Furnace D Size Cabinet O Ou ut tl li in ne e D Dr ra aw wi in ng gs s ...
Страница 102: ...102 88 A951X001 1D EN N No ot te es s ...
Страница 103: ...88 A951X001 1D EN 103 N No ot te es s ...