Maximum Vent Length Table
A951X
Maximum Vent Length Table
Maximum Total Equivalent Length In Feet
for Vent and Inlet Air (See Notes)
Model
2 Inch or 2.5 Inch Pipe
3 Inch or 4 Inch Pipe
Altitude 0–2,000 Feet
A951X040BU3SAB, A951X040BD3SAB,
A951X060BD3SAB, A951X060BU4SAB
200
200
A951X080BU4SAB, A951X080BD4SAB,
A951X080CU5SAB
100
200
A951X100CU5SAB, A951X100CD5SAB
50
200
A951X120DU5SAB, A951X120DD5SAB
Note 1
200
Altitude 2,001–5,400 Feet
A951X040BU3SAB, A951X040BD3SAB,
A951X060BD3SAB, A951X060BU4SAB
200
200
A951X080BU4SAB, A951X080BD4SAB,
A951X080CU5SAB
80
120
A951X100CU5SAB, A951X100CD5SAB
50
150
A951X120DU5SAB, A951X120DD5SAB
Note 1
200
Altitude 5,401–7,800 Feet
A951X040BU3SAB, A951X040BD3SAB,
A951X060BD3SAB, A951X060BU4SAB
100
150
A951X080BU4SAB, A951X080BD4SAB,
A951X080CU5SAB
50
70
A951X100CU5SAB, A951X100CD5SAB
Note 1
100
A951X120DU5SAB, A951X120DD5SAB
Note 1
100
Altitude 7,801–10,100 Feet
A951X040BU3SAB, A951X040BD3SAB,
A951X060BD3SAB, A951X060BU4SAB
50
90
A951X080BU4SAB, A951X080BD4SAB,
A951X080CU5SAB
Note 1
50
A951X100CU5SAB, A951X100CD5SAB
Note 1
50
A951X120DU5SAB, A951X120DD5SAB
Note 1
50
Notes:
1.
Not allowed
2.
For PolyPro® by Duravent, Z-DENS by Novaflex Group, InnoFlue®by Centrotherm, and Polyflue™ manufactured modular venting systems
that are in the approved vent pipe material table, fitting equivalent vent lengths may be different from what is shown in Note 6. Refer to the
venting system manufacturer’s installation instruction for appropriate venting diameters and equivalent lengths.
3.
Minimum vent length for all models: 15' equivalent.
4.
DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace).
If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See note 7
below for exception). The inlet pipe can be of a larger diameter, but never smaller than the vent pipe.
5.
MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF
EACH (Vent or Inlet air pipes).
6.
One SHORT radius 90° elbow is equivalent to 10' of 4" pipe, 10' of 3" pipe, or 8’ of 2" pipe. One LONG radius elbow is equivalent to 6' of 4"
pipe, 7’ of 3" pipe, or 5' of 2" pipe. Two 45° elbows equal one 90° LONG elbow. One MITERED elbow is equivalent to 12’ of 3” pipe or 12’ of
2” pipe.
7.
The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA or BAYAIR30CNVENT termination kit
is used, the equivalent length of pipe is 5 feet. For BAYVENT200B and BAYVENTCN200B the equivalent length is 0 feet.
8.
For Canadian applications, venting systems must meet ULC-S636 requirements.
9.
The INLET AIR of one pipe systems require the installation of a minimum of one 90° elbow (to prevent dust and debris from falling straight
into the furnace).
F
Fu
urrn
na
acce
e G
Ge
en
ne
erra
all IIn
nsstta
alllla
attiio
on
n
Содержание A951X040BD3SAB
Страница 13: ...88 A951X001 1D EN 13 Outline Drawings Upflow Furnace B Size Cabinet ...
Страница 14: ...14 88 A951X001 1D EN Upflow Furnace C Size Cabinet O Ou ut tl li in ne e D Dr ra aw wi in ng gs s ...
Страница 15: ...88 A951X001 1D EN 15 Upflow Furnace D Size Cabinet O Ou ut tl li in ne e D Dr ra aw wi in ng gs s ...
Страница 16: ...16 88 A951X001 1D EN Downflow Furnace B Size Cabinet O Ou ut tl li in ne e D Dr ra aw wi in ng gs s ...
Страница 17: ...88 A951X001 1D EN 17 Downflow Furnace C Size Cabinet O Ou ut tl li in ne e D Dr ra aw wi in ng gs s ...
Страница 18: ...18 88 A951X001 1D EN Downflow Furnace D Size Cabinet O Ou ut tl li in ne e D Dr ra aw wi in ng gs s ...
Страница 102: ...102 88 A951X001 1D EN N No ot te es s ...
Страница 103: ...88 A951X001 1D EN 103 N No ot te es s ...