88-A951X001-1D-EN
29
Vent Terminations
For
DIRECT VENT APPLICATION:
The Furnaces must be vented to
the exterior of the house and combustion air MUST come through the
inlet air pipe from OUTSIDE AIR.
Note:
BAYVENT* accessories can be used for inlet and outlet
terminals when the pipes do not exit the structure together. For
Canadian applications, venting systems must meet ULC-S636
requirements.
For
NONDIRECT VENT APPLICATION:
The Furnace shall be vented
to the exterior of the house, but combustion air may enter from the
surrounding area as long as combustion air requirements are met.
(See AIR FOR COMBUSTION AND VENTILATION)
Vent terminations
•
BAYVENT200B
•
BAYAIR30AVENTA
Vent terminations — Canadian applications. Meets ULC-S636
requirements.
•
BAYVENTCN200B
•
BAYAIR30CNVENT
FURNACE VENT / INLET PIPE INSTALLATION IN TWO
PRESSURE ZONE CONFIGURATIONS ARE NOT ALLOWED
Note:
For single pressure zone applications, see the Horizontal
Venting section.
The following are
EXAMPLES ONLY.
EX. 1 —
Example 1 shows the vent pipe exhausting through the roof and the
inlet air coming from the interior of the house. The inlet air coming
from the interior of the house must meet combustion requirements for
area, etc., as shown in the section AIR FOR COMBUSTION AND
VENTILATION in this Installer’s Guide.
Note:
If only the flue gas pipe is to the outside of the structure, a
straight section of pipe (long enough to exit the Furnace
cabinet) must be attached to the inlet air side with an elbow
(which is 5 to 10 equiv. ft.) installed on the end to prevent dust
and debris from falling directly into the Furnace.
Furnace
Vent
Air
Inlet
EX. 2 —
The inlet air does not have to come from outside the structure.
Example 2 shows the inlet air, may come from the attic if the
requirements for combustion air are met as shown in the section AIR
FOR COMBUSTION AND VENTILATION.
Note:
If only the flue gas pipe is to the outside of the structure, a
straight section of pipe (long enough to exit the Furnace
cabinet) must be attached to the inlet air side with an elbow
(which is 5 to 10 equiv. ft.) installed on the end to prevent dust
and debris from falling directly into the Furnace.
Furnace
Air
Inlet
Vent
Attic
Vent
(See Note)
Attaching Vent Piping
VENT FITTING MATERIAL – PLASTIC
Gas and liquid tight single wall vent fittings, designed for resistance to
corrosive flue condensate, MUST be used throughout.
Listed in the Approved Vent Pipe Materials table are designations for
different types of 2" and 3" size pipe and fittings that meet these
requirements. The materials listed are various grades of PVC, CPVC,
ABS, PolyPro® by DuraVent , Z-Dens by Novaflex Group, Innoflue®
by Centrotherm, and PolyFlue™ polypropylene venting systems.
F
Fu
urrn
na
acce
e G
Ge
en
ne
erra
all IIn
nsstta
alllla
attiio
on
n
Содержание A951X040BD3SAB
Страница 13: ...88 A951X001 1D EN 13 Outline Drawings Upflow Furnace B Size Cabinet ...
Страница 14: ...14 88 A951X001 1D EN Upflow Furnace C Size Cabinet O Ou ut tl li in ne e D Dr ra aw wi in ng gs s ...
Страница 15: ...88 A951X001 1D EN 15 Upflow Furnace D Size Cabinet O Ou ut tl li in ne e D Dr ra aw wi in ng gs s ...
Страница 16: ...16 88 A951X001 1D EN Downflow Furnace B Size Cabinet O Ou ut tl li in ne e D Dr ra aw wi in ng gs s ...
Страница 17: ...88 A951X001 1D EN 17 Downflow Furnace C Size Cabinet O Ou ut tl li in ne e D Dr ra aw wi in ng gs s ...
Страница 18: ...18 88 A951X001 1D EN Downflow Furnace D Size Cabinet O Ou ut tl li in ne e D Dr ra aw wi in ng gs s ...
Страница 102: ...102 88 A951X001 1D EN N No ot te es s ...
Страница 103: ...88 A951X001 1D EN 103 N No ot te es s ...