Indel motion boards
Installation
6.1.1
Notes on UL directive
Motor overload protection
External motor overload protection must be provided by the user.
Additional overload protection is provided for motors by means of temperature sensors in the field
winding. The user is responsible for applying this overload protection.
Only use UL-certified copper wires for 75°C.
UL fuses and cable cross-sections
The controller requires a fuse in the supply line. Only use UL-certified fuses and holders. Triggering
characteristic “K”.
Safety
Cable
fuse
cross-section
A
mm
2
AWG
5
1
17
10
1
17
25
6
9
25
6
9
Manufacturers of UL-certified safety fuses:
●
FS Ferraz Shawmut
●
Limitron KTK from Bussmann
6.1.2
Braking resistance
There is no braking resistor on the MAX2 board. The external braking resistor must be secured
against thermal overload.
Supply: 48V
Ballast 0%
Ucc = 50V
Ballast 100%
Ucc = 52V
Supply: 24V
Ballast 0%
Ucc = 25V
Ballast 100%
Ucc = 27V
For resistance values for the braking resistor see technical details.
Rev 1.31; 04/11/2013
Page 45/54