Chapter 7 Usage of Various Functions
7-
ై
(c) Fig 2.10 shows examples of process control by forward and reverse actions, respectively.
Fig. 2-10 PV of forward / reverse action
f)
Reference value
In general feedback control system shown as the Figure 2-10, the deviation value is obtained by the difference of
PV and SV. P, I, and D operations are performed based on this deviation value. However, each of P, I, and D
operations use different deviation values according to the characteristics of each control actions. The expression
of PID control is as following;
⎥⎦
⎤
⎢⎣
⎡
+
+
=
∫
t
dt
dEd
Td
ds
s
Ei
Ti
Ep
K
MV
0
)
(
1
MV : Manipulate value
K: Proportional gain
Ti: Integral time
Td : Derivative time
Ep: Deviation value for proportional action
Ei: Deviation value for integral action
Ed: Deviation value for derivative action
The deviation values of P, I, and D action is described as following equations;
PV
Ed
PV
SV
Ei
PV
SV
b
Ep
−
=
−
=
−
×
=
The b of the first equation is called as reference value. It can be varied according to the load disturbance of
measurement noise.
Fig. 2-11 Diagram of simple feedback system
Process
-1
+
SV
PV
MV
PID
Содержание K7 Series
Страница 1: ...User s Manual Programmable Logic Controller IMO K7 IMO Precision Controls...
Страница 21: ...Chapter 4 Names of Parts 4 4 1 2 30 points base unit 4 1 3 40 points base unit 4 1 4 60 points base unit...
Страница 57: ...Chapter 6 Input and Output Modules 6 3 40 point base unit 4 60 point base unit DC24V DC24V DC24V DC24V...
Страница 166: ...Chapter8 Communication Function 8 43 Set parameters like the following table and click OK button Program...
Страница 189: ...Chapter 8 Communication Function 8 66 You can see the framelist which is designated Click OK button...
Страница 234: ......