Chapter 7 Usage of Various Functions
7-
ొ
6) Program Example
(1)
System configuration
(2)
Initial setting
a)
PID operation parameters
Auto / Manual operation setting : Auto
Forward
/
Reverse operation : Forward
SV setting : 960(60
°
C ),1120(70
°
C ),1280(80
°
C ),1600 (100
°
C)
Current value setting : D4980(AD conversion value of AD module Ch1)
BIAS setting : 0 (If only P control is used, input proper value other 0)
EN_P, EN_I, EN_D setting: EN_P=1, EN_I=1, EN_D=1 (PID operation)
REF=10 , TT=50 , N=1
MV_MAX, MV_MIN, MVMAN : MV_MAX=4000, MC_MIN=0, MAMAN=2000
S_TIME : S_TIME=100 (sampling time = 10 seconds)
b)
Auto-tuning parameters
PV setting: : 960(60
°
C ),1120(70
°
C ),1280(80
°
C ),1600 (100
°
C )
S_TIME : S_TIME=100 (sampling time = 10 seconds)
Current value setting : D4980(AD conversion value of AD module Ch1)
wave select : designation value=1
c)
A/D module setting
Channel setting : use channel 1
input range setting : DC 4 ~ 20 mA
A/D conversion data registration area : D4980
Output data type: – 48 ~ 4047
d)
D/A module setting
output range setting: DC 4 ~ 20 mA
D/A conversion data registration area : D4982
K7 Base unit
RS-232C
Transformer
Heater
Temp. Sensor
Signal transforming
device
PV: DC4~20mA
(1~5V)
MV: DC4~20mA
(1~5V)
G7F-ADHA
KGLWIN
(V2.0 or later)
Electric oven
(0 ~ 200
°
C)
Содержание K7 Series
Страница 1: ...User s Manual Programmable Logic Controller IMO K7 IMO Precision Controls...
Страница 21: ...Chapter 4 Names of Parts 4 4 1 2 30 points base unit 4 1 3 40 points base unit 4 1 4 60 points base unit...
Страница 57: ...Chapter 6 Input and Output Modules 6 3 40 point base unit 4 60 point base unit DC24V DC24V DC24V DC24V...
Страница 166: ...Chapter8 Communication Function 8 43 Set parameters like the following table and click OK button Program...
Страница 189: ...Chapter 8 Communication Function 8 66 You can see the framelist which is designated Click OK button...
Страница 234: ......