Chapter 7 Usage of Various Functions
7-
ే
Chapter 7 Usage of Various Functions
7.1 Built-in Functions
7.1.1 High-speed counter function
This chapter describes the specification, handling, and programming of built-in high speed counter of K7. The built-in
high speed counter of MK80S(hereafter called HSC) has the following features;
3 counter functions as followings
- 1-phase up / down counter : Up / down is selected by user program
- 1-phase up / down counter : Up / down is selected by external B phase input
- 2-phase up / down counter : Up / down is automatically selected by the phase difference between A-phase and B.
Multiplication (1, 2, or 4) with 2-phase counter
- 2-phase pulse input multiplied by one
: Counts the pulse at the leading edge of A-phase.
- 2-phase pulse input multiplied by two
: Counts the pulse at the leading / falling edge of A-phase.
- 2-phase pulse input multiplied by four
: Counts the pulse at the leading / falling edge of A-phase and B
1)
Performance Specifications
Items
Specifications
Types
A-phase, B-phase, Preset
Rated level
24VDC (15mA)
Input signal
Signal type
Voltage input
Counting range
0 ~ 16,777,215 (Binary 24 bits)
Max. counting speed
1-phase 16kHz/ 2-phase 8kHz
1-phase
Sequence program or B-phase input
Up / Down
selection
2-phase
Auto-select by phase difference of A-phase and B
Multiplication
1, 2, or 4
Preset input
Sequence program or external preset input
2)
Input specification
Items
Specifications
Rated input
24VDC (15mA)
On voltage
14VDC or higher
A / B phase
Off voltage
2.5VDC or lower
Rated input
24VDC (15mA)
On voltage
19VDC or higher
Off voltage
6V or lower
On delay time
Less than 1.5ms
Preset input
Off delay time
Less than 2ms
Содержание K7 Series
Страница 1: ...User s Manual Programmable Logic Controller IMO K7 IMO Precision Controls...
Страница 21: ...Chapter 4 Names of Parts 4 4 1 2 30 points base unit 4 1 3 40 points base unit 4 1 4 60 points base unit...
Страница 57: ...Chapter 6 Input and Output Modules 6 3 40 point base unit 4 60 point base unit DC24V DC24V DC24V DC24V...
Страница 166: ...Chapter8 Communication Function 8 43 Set parameters like the following table and click OK button Program...
Страница 189: ...Chapter 8 Communication Function 8 66 You can see the framelist which is designated Click OK button...
Страница 234: ......