Chapter8 Communication Function
8-11
Ex.2
If number of data is H04 and the data is H12345678, ASCII code converted value of this is "31 32 33 34 35 36 37
38," and this contents is entered in data area. Name directly, highest value is entered first, lowest value last.
Remark
1) If data type is Bit, data read is indicated by bytes of hex. Namely, if Bit value is 0, it indicated by H00, and if
1, by H01.
(4)
Response format (NAK response)
Format name
Header
Station No.
Command
Command type
Error code
(Hex 2 Byte)
Tail
Frame check
Ex. of frame
NAK
H20
R(r)
SS
H1132
ETX
BCC
ASCII value
H15
H3230
H52(72)
H5353
H31313332
H03
Item
Explanation
BCC
When command is lowercase(r), only one lower byte of the value resulted by adding 1
Byte each to ASCII values from NAK to ETX is converted into ASCII and added to BCC.
Error code
Hex and 2 bytes(ASCII code, 4 bytes) indicate error type. For the details, see 8.1.8 Error
codes.