Chapter8 Communication Function
8-1
Chapter 8 Communication Function
8.1 Dedicated Protocol Communication
8.1.1 Introduction
MK80S’ s built-in Cnet communication uses only K7 base unit for a dedicated communication. That is, it
doesn’ t need a separate Cnet I/F module to facilitate the user-intended communication system by utilizing
reading or writing of any area in CPU, and monitoring function.
MK80S base unit serves as follows:
•
Individual/continuous reading of device
•
Individual/continuous writing of device
•
Reading CPU status
•
Monitor devices registration
•
Executing monitoring
•
1:1 connection(link between K’ series) system configuration (K7 base unit:
RS-232C)
Remark
K7 built-in communication function supports Cnet communication without any separate Cnet module. It
must be used under the following instructions.
1)
K7 base unit supports 1:1 communication only. for 1:N system having master-slave Format, use
K7 base unit with G7L-CUEC module connected. G7L-CUEC module supports RS-422/485 protocol.
2)
RS-232C communication cable for K7 base unit is different from RS-232C cable for KGL_WIN in pin
arrangement and from the cable for Cnet module, too. The cable can’ t be used without any treatment. For
the detailed wiring method, refer to 8.1.2.
3)
It’ s possible to set baud rate type and M area size in KGL_WIN. For the detailed information, refer to the
appendix or KGLWIN manual.
Содержание K7 Series
Страница 1: ...User s Manual Programmable Logic Controller IMO K7 IMO Precision Controls...
Страница 21: ...Chapter 4 Names of Parts 4 4 1 2 30 points base unit 4 1 3 40 points base unit 4 1 4 60 points base unit...
Страница 57: ...Chapter 6 Input and Output Modules 6 3 40 point base unit 4 60 point base unit DC24V DC24V DC24V DC24V...
Страница 166: ...Chapter8 Communication Function 8 43 Set parameters like the following table and click OK button Program...
Страница 189: ...Chapter 8 Communication Function 8 66 You can see the framelist which is designated Click OK button...
Страница 234: ......