Chapter 8 Communication Function
8-48
8.2.2 Parameter Setting
1) Setting Communications Parameter
(1) Open a new project file from KGLWIN
Select K7 as PLC type
(2) After setting communication parameter at KGLWIN. Double click it to activate this window.
(3) Set according to the following table.
Item
Setting range
Station No.
Station no. from 0 to 31.
Baud Rate
1200, 2400, 4800, 9600, 19200, 38400, 57600 bps
Data Bit
7 or 8 bits
Parity Bit
0, Even or Odd
Stop Bit
1 or 2 bit(s)
Communication
Channel
RS232C Null Modem or RS422/485 : It’ s a communication channel for the communication, using
MK80S base unit’ s built-in communication and Cnet I/F module (G7L-CUEC).
RS232C Modem (Dedicated Line) : It’ s to be selected for the communication, using an dedicated
modem with Cnet I/F module (G7L-CUEB).
RS232C Dial Up Modem : It’ s to be selected for the general communication connecting through
the telephone line by dial up modem and Cnet I/F module (G7L-CUEB).
Footnote) Using Cnet I/F module (G7L-CUEB) supporting RS232C, RS232C dedicated or
dial-up modem communication can be done, but not through Cnet I/F module (G7L-
CUEC) supporting RS422/485.
Timeout in Master
Mode
It’ s the time waiting a responding frame since the master MK80S base unit sends a request
frame.
The default value is 500ms.
It must be set in consideration of the max. periodical time for sending/receiving of the master
PLC.
If it’ s set smaller than the max. send/receive periodical time, it may cause communication error.
User Define Master
/ Slave
If it is set as the master, it’ s the subject in the communication system. If it’ s set as the slave,
it only responds to the request frame of the master.
Содержание K7 Series
Страница 1: ...User s Manual Programmable Logic Controller IMO K7 IMO Precision Controls...
Страница 21: ...Chapter 4 Names of Parts 4 4 1 2 30 points base unit 4 1 3 40 points base unit 4 1 4 60 points base unit...
Страница 57: ...Chapter 6 Input and Output Modules 6 3 40 point base unit 4 60 point base unit DC24V DC24V DC24V DC24V...
Страница 166: ...Chapter8 Communication Function 8 43 Set parameters like the following table and click OK button Program...
Страница 189: ...Chapter 8 Communication Function 8 66 You can see the framelist which is designated Click OK button...
Страница 234: ......