Chapter8 Communication Function
8-46
(Continued)
Error code
Error type
Error condition and causes
Treatment
H6001
Syntax error
* When use commands that aren’ t supported.
Ex1) When use device
like %MX100 in RSB command
* Be familiar with the manual.
* Check if the system stopped.
* reset
H6010
Syntax error
* OVER-RUN, FRAME error
* Be familiar with the manual.
H6020
Syntax error
* TIME_OUT error
* Confirm the setting of the communication
ports of RS-232C.
* reset
H6030
Syntax error
* Syntax error in commands
* Check if each sends frame has ENQ, EOT.
H6040
Syntax error
When a FRAME text exceeds over 256 bytes.
* Rearrange send frame not to go over 256
bytes.
H6050
Syntax error
* BCC error
* Check if BCC is right.