Chapter 6 Input and Output Modules
6-
10
6.3.2 Expansion Module
1) Specifications
Expansion Module
Model
Specifications
G7E-DR10A
Output point
4 points
Insulation method
Relay insulation
Rated load
Voltage/current
DC24V / 2A (r/load), AC220V / 2A (COS
Ψ
= 1) / 1 point 5A / 1COM
Min. load Voltage/current
DC5V / 1mA
Max. load voltage/current
AC250V, DC110V
Current leakage when off
0.1mA (AC220V, 60Hz)
Max. On/off frequency
1,200/hr
Surge Absorber
None
Mechanical
More than 20,000,000
Rated on/off voltage/current load 100,000 or more
AC200V / 1.5A, AC240V / 1A (COS
Ψ
= 0.7) 100,000 or more
AC200V / 1A, AC240V / 0.5A (COS
Ψ
= 0.35) 100,000 or more
Life
Electrical
DC24V / 1A, DC100V / 0.1A (L / R = 7ms) 100,000 or more
Off
→
On
10 ms or less
Response time
On
→
Off
12 ms or less
Common method
1 point/ 1COM, 2 points/ 1COM
Operation indication
LED is on at on status of output
2) Circuit
It’ s the same with the output circuit of the base unit.
3) Output wiring
REMARK
1) Refer to 7.2 ‘ Special Functions’ for the special function units
DC5V
L
L
L
L
DC24V
AC110/220V
Содержание K7 Series
Страница 1: ...User s Manual Programmable Logic Controller IMO K7 IMO Precision Controls...
Страница 21: ...Chapter 4 Names of Parts 4 4 1 2 30 points base unit 4 1 3 40 points base unit 4 1 4 60 points base unit...
Страница 57: ...Chapter 6 Input and Output Modules 6 3 40 point base unit 4 60 point base unit DC24V DC24V DC24V DC24V...
Страница 166: ...Chapter8 Communication Function 8 43 Set parameters like the following table and click OK button Program...
Страница 189: ...Chapter 8 Communication Function 8 66 You can see the framelist which is designated Click OK button...
Страница 234: ......