Technical data
A.3 Technical data: FL1F-M08C2R2
IDEC SmartRelay Manual
288
Input voltage L1
•
Signal 0
•
Signal 1
•
Signal 0
•
Signal 1
•
< 40 VAC
•
> 79 VAC
•
< 30 VDC
•
> 79 VDC
Input current at
•
Signal 0
•
Signal 1
•
Signal 0
•
Signal 1
•
< 0.05 mA AC
•
> 0.08 mA AC
•
< 0.06 mA DC
•
> 0.13 mA DC
Delay time at 0 to 1:
•
120 VAC
•
240 VAC
•
120 VDC
•
240 VDC
Delay time at 1 to 0:
•
120 VAC
•
240 VAC
•
120 VDC
•
240 VDC
•
Typ. 40 ms
•
Typ. 30 ms
•
Typ. 25 ms
•
Typ. 20 ms
•
Typ. 45 ms
•
Typ. 70 ms
•
Typ. 60 ms
•
Typ. 75 ms
Line length (unshielded)
Max. 100 m
Digital outputs
Number
4
Output type
Relay outputs
Electrical isolation
Yes
In groups of
1
Control of a digital input
Yes
Continuous current I
th
Recommended range of application ≥ 100 mA at
12 VAC/VDC
Max. 5 A per relay
Surge current
Max. 30 A
Incandescent lamp load (25000 switching cycles)
at:
230/240 VAC
100/120 VAC
1000 W
500 W
Fluorescent tubes with ballast (25000 switching
cycles)
10 x 58 W (at 230/240 VAC)
Fluorescent tubes, conventionally compensated
(25000 switching cycles)
1 x 58 W (at 230/240 VAC)
Fluorescent tubes, uncompensated (25000
switching cycles)
10 x 58 W (at 230/240 VAC)
Short circuit-proof cos 1
Power protection B16, 600 A
Short circuit-proof cos 0.5 to 0.7
Power protection B16, 900 A
Derating
None; across the entire temperature range
Parallel output circuits for power increase
Not permitted
FL1F-M08C2R2