IDEC SmartRelay Manual
133
IDEC SmartRelay functions
4.4 Special functions list - SF
Parameter T
Note the defaults for parameter T in topic Time response (Page 124).
The actual value of another already-configured functions can provide the time for parameter
T. You can use the actual values of the following functions for the value of T:
•
Analog comparator (Page 183)(actual value Ax - Ay)
•
Analog trigger (Page 178)(actual value Ax)
•
Analog amplifier (Page 191)(actual value Ax)
•
Analog multiplexer (Page 209)(actual value AQ)
•
Analog ramp control (Page 212)(actual value AQ)
•
Analog Math (Page 224) (actual value AQ)
•
PI controller (Page 216)(actual value AQ)
•
Up/down counter (Page 168)(actual value Cnt)
•
Analog filter (Page 229) (actual value AQ)
•
Average value (Page 235) (actual value AQ)
•
Max/Min (Page 231) (actual value AQ)
•
On-delay (current time Ta)
•
Off-delay (Page 136)(current time Ta)
•
On-/off-delay (Page 138)(current time Ta)
•
Retentive on-delay (Page 140)(current time Ta)
•
Interval time-delay relay/Pulse output (Page 142)(current time Ta)
•
Edge-triggered interval time-delay relay (Page 144)(current time Ta)
•
Asynchronous pulse generator (Page 146)(current time Ta)
•
Stairwell light switch (Page 150)(current time Ta)
•
Dual-function switch (Page 152)(current time Ta)
•
Stopwatch (Page 166)(actual value AQ)
•
Frequency trigger (Page 175) (actual value Fre)
Select the required function by the block number. The timebase is configurable.
Valid ranges of the timebase, if T = parameter
Note the following characteristics of timebase values.
Timebase
max. value
min. resolution
Accuracy
s (seconds)
99:99
10 ms
+ 10 ms
m (minutes)
99:59
1s
+ 1 s
h (hours)
99:59
1 min
+ 1 min