![IDEC SMARTRELAY Скачать руководство пользователя страница 304](http://html.mh-extra.com/html/idec/smartrelay/smartrelay_user-manual_617404304.webp)
Technical data
A.6 Technical data: FL1F-H12RCA/B12RCA
IDEC SmartRelay Manual
292
A.6
Technical data: FL1F-H12RCA/B12RCA
FL1F-H12RCA
FL1F-B12RCA
Power supply
Input voltage
24 VAC/VDC
Permissible range
20.4 VAC to 26.4 VAC
20.4 VDC to 28.8 VDC
Reverse polarity protection
- -
Permissible mains frequency
47 Hz to 63 Hz
Power consumption
•
24 VAC
•
24 VDC
•
15 mA to 150 mA
•
15 mA to 130 mA
Voltage failure buffering
Typ. 5 ms
Power loss
•
24 VAC
•
24 VDC
•
0.4 W to 3.6 W
•
0.4 W to 3.2 W
Backup of the real-time clock at 25 °C
Typ. 20 days
Accuracy of the real-time clock
Typ. ± 2 s/day
Digital inputs
Number
8, optional positive voltage or negative voltage
Electrical isolation
No
Number of high speed inputs
0
Input frequency
•
Normal input
•
High speed input
•
Max. 4 Hz
•
- -
Max. continuous permissible voltage
26.4 VAC
28.8 VDC
Input voltage
•
Signal 0
•
Signal 1
L
•
< 5 VAC/VDC
•
> 12 VAC/VDC
Input current at
•
Signal 0
•
Signal 1
•
< 1.2 mA
•
> 2.6 mA
Delay time at
•
0 to 1
•
1 to 0
•
Typ. 1.5 ms
•
Typ. 15 ms
Line length (unshielded)
Max. 100 m
Analog inputs
Number
- -
Range
- -
max. Input voltage
- -
Digital outputs
Number
4
Output type
Relay outputs
Electrical isolation
Yes
In groups of
1