IDEC SmartRelay Manual
191
IDEC SmartRelay functions
4.4 Special functions list - SF
4.4.22
Analog amplifier
Short description
This special function amplifies the value of an analog input and outputs the result at an analog
output.
Gain and offset parameters
Please note the information on gain and offset parameters in topic Calculating the gain and
offset of analog values (Page 126).
Parameter p (number of decimals)
Applies only to the A value in a message text.
Functional description
The function fetches the analog signal of input Ax.
This value is multiplied by the value of the A (gain) parameter, and parameter B (offset) is
then added to the product: (Ax gain) offset actual value Ax.
The actual value Ax is output at A .
Symbol in
IDEC SmartRelay
iring
Description
Input Ax
Input Ax is one of the following analog signals:
AI1 to AI8 ( )
AM1 to AM64
NAI1 to NAI32
A 1 to A 8
NA 1 to NA 16
Block number of a function with analog output
Parameter
A: gain
Range of values: -10.00 to 10.00
B: zero offset
Range of values: -10,000 to 10,000
p: number of decimals
Range of values: 0, 1, 2, 3
Output A
This special function has an analog output. This
output can only be connected with analog inputs,
analog memory markers, analog outputs or network
analog outputs.
Range of values for A :
-32767 to 32767
AI1...AI8: 0 V to 10 V corresponds with 0 to 1000 (internal value).
$ᇄ
$4
$[
3DU
$QDORJ$PSOLILHU