![IDEC SMARTRELAY Скачать руководство пользователя страница 306](http://html.mh-extra.com/html/idec/smartrelay/smartrelay_user-manual_617404306.webp)
Technical data
A.7 Technical data: FL1F-M08D2R2
IDEC SmartRelay Manual
294
A.7
Technical data: FL1F-M08D2R2
FL1F-M08D2R2
Power supply
Input voltage
24 VAC/VDC
Permissible range
20.4 VAC to 26.4 VAC
20.4 VDC to 28.8 VDC
Reverse polarity protection
- -
Permissible mains frequency
47 Hz to 63 Hz
Power consumption
•
24 VAC
•
24 VDC
•
20 mA to 100 mA
•
8 mA to 50 mA
Voltage failure buffering
Typ. 5 ms
Power loss
•
24 VAC
•
24 VDC
•
0.5 W to 2.4 W
•
0.2 W to 1.2 W
Digital inputs
Number
4, optional positive voltage or negative voltage
Electrical isolation
No
Number of high speed inputs
0
Input frequency
•
Normal input
•
High speed input
•
Max. 4 Hz
•
- -
Max. continuous permissible voltage
•
26.4 VAC
•
28.8 VDC
Input voltage
•
Signal 0
•
Signal 1
L
•
< 5 VAC/VDC
•
> 12 VAC/VDC
Input current at
•
Signal 0
•
Signal 1
•
< 1.1 mA
•
> 2.63 mA
Delay time at
•
0 to 1
•
1 to 0
•
Typ. 1.5 ms
•
Typ. 15 ms
Line length (unshielded)
Max. 100 m
Digital outputs
Number
4
Output type
Relay outputs
Electrical isolation
Yes
In groups of
1
Control of a digital input
Yes
Continuous current I
th
Recommended range of application ≥ 100 mA at
12 VAC/VDC
Max. 5 A per relay
Surge current
Max. 30 A
Incandescent lamp load (25000 switching cycles)
at
1000 W