Mounting the Text Display
To prepare the mounting surface for the optional Text Display and mount it, follow these
steps:
1. Cut a 119 mm × 78.5 mm (tolerance: +0.5 mm) hole in the mounting surface.
2. Place the included gasket on the frontplate of the Text Display.
3. Fit the Text Display into the cutout you made in the mounting surface.
4. Attach the mounting brackets (included) to the Text Display
5. Tighten the mounting screws on the mounting brackets to 0.2 Nm torque to secure the
Text Display.
You can then connect the Text Display to the Base Module through the Ethernet interface.
Note
Make sure you mount the Text Display vertically on a flat surface of an IP 65 or Type 4X/12
enclosure.