IDEC SmartRelay Manual
27
IDEC SmartRelay installation and wiring
2.3 Wiring IDEC SmartRelay
For 2-cable connection
2.3.1
Connecting the power supply
The 100-240 VAC/VDC versions of IDEC SmartRelay are suitable for operation with rated
voltages of 100 VAC/VDC and 240 VAC/VDC. The IDEC SmartRelay 24 V and 12 V versions
can be operated with a 24 VDC, 24 VAC or 12 VDC power supply. For information on
permissible voltage tolerances, line frequencies and power consumption, refer to the
installation instructions in the Product Information supplied with your device and to the
technical data in Appendix A.
The Text Display must be supplied with a voltage of 12 VDC or 24 VAC/VDC.
Cross-section
[mm
2
]
AWG
Phoenix Contact
Ferrule type No.
0.3
22
AI-TWIN2X0,5-8WH
0.5
20
AI-TWIN2X0,5-8WH
0.75
18
AI-TWIN2X0,75-8GY
1.25
18
AI-TWIN2X1,5-8BK
Recommended
crimping tool
CRIMPFOX ZA 3
Note
Always cover the terminals after you have completed the installation. To protect IDEC
SmartRelay adequately from impermissible contact to live parts, comply with local standards.
CAUTION
Expansion modules FL1F-M08C2R2 must be operated with the same type of power supply
(DC or AC) as for the connected 100-240 VAC/VDC version of the Base Module. The same
supply output "+/- "on DC power supplies or "N/L" on AC power supplies must connect to the
same phase on both the expansion module FL1F-M08C2R2 and the connected FL1F-
H12RCC/B12RCC. Failure to follow the instructions could result in personal injury.
Note
A power failure might cause an additional edge triggering signal at the special functions. The
stored data will be from the last uninterrupted cycle.
When using different power supplies, supply power to the base module and expansion
modules at the same time, or supply power to expansion modules before the base module.
When supplying power to expansion modules after the base module, expansion modules
may not be recognized by the base module.
When using different power supplies, the fast transient/burst immunity (IEC61000-4-4) will be
1kV (power supply).
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]