Technical data
A.7 Technical data: FL1F-M08D2R2
Notice: For fluorescent lamps with capacitors, you must consider the technical data of
fluorescent lamp ballasts. If the current exceeds the maximum allowed surge current,
appropriate contactor relays must switch the flourescent lamps.
Fluorescent tubes with ballast (25000 switching
cycles)
10 x 58 W
Fluorescent tubes, conventionally compensated
(25000 switching cycles)
1 x 58 W
Fluorescent tubes, uncompensated (25000
switching cycles)
10 x 58 W
Derating
None; across the entire temperature range
Short circuit-proof cos 1
Power protection B16, 600 A
Short circuit-proof cos 0.5 to 0.7
Power protection B16, 900 A
Parallel output circuits for power increase
Not permitted
Protection of output relay (if desired)
Max. 16 A,
characteristic B16
Switching rate
Mechanical
10 Hz
Ohmic load/lamp load
2 Hz
Inductive load
0.5 Hz
FL1F-M08D2R2