IDEC SmartRelay functions
4.4 Special functions list - SF
IDEC SmartRelay Manual
136
4.4.2
Off-delay
Short description
hen an On-delay (Page 132) is set, the output is reset when the configured time has expired.
Parameter T
Note the parameter T defaults specified in topic Time response (Page 124).
The actual value of another already-configured functions can provide the time for parameter
T. ou can use the actual value of the following functions:
Analog comparator (Page 183) (actual value Ax - Ay)
Analog trigger (Page 178) (actual value Ax)
Analog amplifier (Page 191) (actual value Ax)
Analog multiplexer (Page 209) (actual value A )
Analog ramp control (Page 212) (actual value A )
Analog Math (Page 224) (actual value A )
PI controller (Page 216) (actual value A )
Up/down counter (Page 168) (actual value Cnt)
Analog filter (Page 229) (actual value A )
Average value (Page 235) (actual value A )
Max/Min (Page 231) (actual value A )
On-delay (Page 132) (current time Ta)
Off-delay (current time Ta)
On-/off-delay (Page 138) (current time Ta)
Retentive on-delay (Page 140) (current time Ta)
Interval time-delay relay/Pulse output (Page 142) (current time Ta)
Edge-triggered interval time-delay relay (Page 144) (current time Ta)
Asynchronous pulse generator (Page 146) (current time Ta)
Stairwell light switch (Page 150) (current time Ta)
Symbol in
IDEC SmartRelay
iring
Description
Input Trg
The off-delay timer starts with a negative edge (1 to 0
transition) at input Trg (Trigger)
Input R
A signal at input R resets the on-delay time and the
output.
Parameter
The output switches off (transitions from1 to 0) when
the delay time T expires.
Retentivity:
/ No retentivity
R The status is retentive.
Output
A signal at input Trg sets . holds this state until T
expires.
4
7UJ
2II'HOD\
3DU