M-7065 User’s Manual
Ver2.0, Dec. /200
8
---
95
40483
Module name (low word)
R
40484
Module name (high word)
R
30001
DI Count Value
R
00270
Host watch dog timeout status, write 1 to
clear host watchdog timeout status.
R/W
40488
Modbus reponse delay time in ms, valid
range:0~30
R/W
40492
Host watchdog timeout count,write 0 to
clear
R/W
00260
Modbus host watchdog mode
0 : same as I-7000
1 : can use AO and DO command to clear
host watchdog timeout status
R/W
00261
1 : enable, 0 : disable host watchdog
R/W
40489
Host watchdog timeout value, 0~255, in
0.1s
R/W
00257
Protocol, 0: DCON, 1: Modbus
R/W
00258
Modbus Protocol Option, 0: RTU, 1:ASCII
R/W
10273
Reset status, 1: first read after powered on,
0 : not the first read after powered on
R
312345, 412345
Informs all modules that the host is OK
R
1.
Modbus RTU Function Description
:
(0xxxx) : 0x01
、
0x05
、
0x0F Function code
(1xxxx) : 0x02 Function code
(3xxxx) : 0x04 Function code
(4xxxx) : 0x03
、
0x03
、
0x10 Function code
2.
Address mapping of PLC(Base 1).