M-7065 User’s Manual
Ver2.0, Dec. /200
8
---
129
3.8.7 34(0x22) Read Digital Input Count Edge
This sub-function code is used to read the digital
input counter trigger edge value of a module.
Request
00
Address
1 Byte
1-2 47
01
Function code
1 Byte
0x46
02
Sub-Function code
1 Byte
0x22
Response:
00
Address
1 Byte
1-2 47
01
Function code
1 Byte
0x46
02
Sub-Function code
1 Byte
0x22
03
Edge setting value
1 Byte
0x00-0xFF (DI0-DI7)
04
Edge setting value
1 Byte
0x00-0xFF (DI8-DI15)
05
Edge setting value
1 Byte
0x00-0xFF (DI16-DI23)
06
Edge setting value
1 Byte
0x00-0xFF (DI24-DI31)
*1 = rising edge, 0 = falling edge. For example 0x03 denotes that channels 0~1 are set
as rising edge and channels 2~3 are set as falling edge
Error Response:
00
Address
1 Byte
1-2 47
01
Function code
1 Byte
0xC6
02
Exception code
1 Byte
Refer to Modbus standard
for more details