3.2 02(0x02) Read discrete inputs
This function code is used to read the current
digital input value.
Request
00
Address
1 Byte
1-2 47
01
Function code
1 Byte
0x02
02-03
Starting channel
numbers
2 Byte
DI : 0x0000-0x001F
04-05
Input channel number
2 Byte
0x0001-0x0020
(Bit count)
Response:
00
Address
1 Byte
1-2 47
01
Function code
1 Byte
0x02
02
Byte Count
1 Byte
Byte count of response
(B=(bit count + 7)/8)
03
Bit values
B Byte
Bit values
Error Response:
00
Address
1 Byte
1-2 47
01
Function code
1 Byte
0x82
02
Exception code
1 Byte
Refer to Modbus standard
for more details