Response:
00
Address
1 Byte
1-2 47
01
Function code
1 Byte
0x05
02-03
Output channel
numbers
2 Byte
The value is the same as
byte 02 and 03 of the
Request
04-05
Output value
2 Byte
The value is the same as
byte 04 and 05 of the
Request
Error Response:
00
Address
1 Byte
1-2 47
01
Function code
1 Byte
0x85
02
Exception code
1 Byte
Refer to Modbus standard
for more details
Examples:
Command:05 05 00 83 FF 00 [ 7C 56 ]
Response:05 05 00 83 FF 00 7C 56
Sets DO3 power-on value to on
Command:05 05 02 00 FF 00 [ 8C 06 ]
Response:05 05 02 00 FF 00 8C 06
Clear digital input count
Command:05 05 00 02 FF 00 [ 2C 7E ]
Response:05 05 00 02 FF 00 2C 7E
Sets DO2 to on