2.3 #AA00(Data)
Description:
Sets the digital output value of the lower eight channels.
(DO0-DO7)
Syntax:
#AA00(Data)[CHKSUM](CR)
#
Delimiter character
AA
Address of the module to be set (00 to FF)
00
Command to set the digital output value of
the lower eight channels. (DO0-DO7)
(Data)
A two-digit hexadecimal value, where bit 0
corresponds to DO0, bit 1 corresponds to
DO1, etc. When the bit is 1, it denotes that
the digital output channel is on, and 0
denotes that the digital output channel is off.
Response:
Valid Command:
>[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
Ignored Command: !
[CHKSUM](CR)
>
Delimiter for a valid command.
?
Delimiter for an invalid command.
!
Ignored Delimiter character.