
M-7065 User’s Manual
Ver2.0, Dec. /200
8
---
40
2.9 $AA4
Description:
Reads the synchronized data that was retrieved by the
last #** command.
Syntax:
$AA4 [CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be set (00 to FF)
4
Command to read the synchronized data
Response:
Valid
Command:
!S[CHKSUM](CR)
Invalid
Command:
?AA[CHKSUM](CR)
!
Delimiter for a valid command.
?
Delimiter for an invalid command.
AA
Address of the responding module (00 to FF)
S
Status of the synchronized data
1
:
first read
0
:
not the first read
(Data)
Synchronized data. See Section 1.2 for the
data format.
Содержание M-7065
Страница 7: ...M 7065 User s Manual Ver2 0 Dec 2008 7 1 2 Pin Assignment...
Страница 42: ...M 7065 User s Manual Ver2 0 Dec 2008 42 Related Commands Section 2 2...
Страница 106: ...M 7065 User s Manual Ver2 0 Dec 2008 106 Supported modules M 7065 Valid starting channel DI Count Value 0x0000 0x0003...