2.1 %AANNTTCCFF
Description:
Sets the configuration of a module.
Syntax:
%AANNTTCCFF[CHKSUM](CR)
%
Delimiter character
AA
Address of the module to be configured in
hexadecimal format (00 to FF)
NN
New address of the module in hexadecimal
format (00 to FF)
TT
Type code, should be 40 for DIO module.
CC
(Baud Rate code, should be 0A for DIO)
FF
Used to set the counter update direction and
checksum (Section 1.1).
Response:
Valid Command:
!AA[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter for a valid command.
?
Delimiter for an invalid command.
AA
Address of the module in hexadecimal
format (00 to FF)