M-7065 User’s Manual
Ver2.0, Dec. /200
8
---
114
3.6 06(0x06) Write multiple registers
This function code is used to set the settings of the
module.
Request
00
Address
1 Byte
1-2 47
01
Function code
1 Byte
0x06
02-03
Address mapping
2 Byte
Sets modbus reponse
delay time : 0x01E7
Clear watchdog timeout
count : 0x01EB
Sets watchdog timeout
value : 0x01E8
04-05
Register value
2 Byte
Register value
Response:
00
Address
1 Byte
1-2 47
01
Function code
1 Byte
06
02-03
Address mapping
2 Byte
The value is the same as
byte 02 and 03 of the
Request
04-05
Register value
2 Byte
Register value
Error Response:
00
Address
1 Byte
1-2 47
01
Function code
1 Byte
0x86
02~
Exception code
n Byte
Refer to Modbus standard
for more details