M-7065 User’s Manual
Ver2.0, Dec. /200
8
---
134
3.8.10 40(0x29) Set DI/O Active Status
This sub-function code is used to set the DI/O
active states of a module.
Request
00
Address
1 Byte
1-2 47
01
Function code
1 Byte
0x46
02
Sub-Function code
1 Byte
0x29
03
DI/O Active Status
1 Byte
0x00-0x03
7
6
5
4
3
2
1
0
Reserved
OAS
IAS
Key
Description
OAS
DO Active Status
0
:
output value 1 for relay active
0
:
output value 0 for relay inactive
1
:
output value 0 for relay active
0
:
output value 1 for relay inactive
IAS
DI Active Status
0
:
input value 1 for non-signal or the low voltage;
0
:
input value 0 for high voltage
1
:
input value 0 for non-signal or the low voltage;
0
:
input value 1 for high voltage
(DI/O Active Status)