M-7065 User’s Manual
Ver2.0, Dec. /200
8
---
43
2.10 $AA5
Description:
Reads the reset status of a module.
Syntax:
$AA5 [CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be set (00 to FF)
5
Command to read the module reset status.
Response:
Valid Command:
!AAS[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter for a valid command.
?
Delimiter for an invalid command.
AA
Address of the responding module (00 to FF)
S
Reset status of the module
1
:
This is the first time the command has
been sent since the module was powered on.
0
:
This is not the first time the command
has been sent since the module was
powered on, which denotes that there has
been no module reset since the last $AA5
command was sent.