M-7065 User’s Manual
Ver2.0, Dec. /200
8
---
51
2.14 $AAF
Description:
Reads the firmware version of a module.
Syntax:
$AAF [CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be set (00 to FF)
F
Command to read the firmware version
Response:
Valid Command:
!AA(Data)[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter for a valid command.
?
Delimiter for an invalid command.
AA
Address of the responding module (00 to FF)
(Data)
Firmware version string of the module
There will be no response if the command syntax is
incorrect, there is a communication error, or there is
no module with the specified address.