M-7065 User’s Manual
Ver2.0, Dec. /200
8
---
131
3.8.8 39(0x27) Set Power-on Value
This sub-function code is used to set the power-on
value of a module.
Request
00
Address
1 Byte
1-2 47
01
Function code
1 Byte
0x46
02
Sub-Function code
1 Byte
0x27
03
Power-on Value
1 Byte
0x00-0xFF (DOI0-DO7)
04
Power-on Value
1 Byte
0x00-0xFF (DO8-DO15)
05
Power-on Value
1 Byte
0x00-0xFF (DO16-DO23)
06
Power-on Value
1 Byte
0x00-0xFF (DO24-DO31)
Response:
00
Address
1 Byte
1-2 47
01
Function code
1 Byte
0x46
02
Sub-Function code
1 Byte
0x27
03
Power-on Value
1 Byte
0 : OK
Others : Error
Error Response:
00
Address
1 Byte
1-2 47
01
Function code
1 Byte
0xC6
02
Exception code
1 Byte
Refer to Modbus standard
for more details