CAN-8123/CAN-8223/CAN-8423 user’s manual (Revision 3.00, May/22/2009) ------
146
Step 6. The communication and generic errors on the error register are
indicated in the received message.
11-bit COB-ID (bit)
Func Code
Node ID
8-byte Data (byte)
10 9 8 7 6 5 4 3 2 1 0
RTR
Data
Length
0
1
2
3 4 5 6 7
1 0 1 1 0 0 0 0 0 0 1
0
8
4F 01 10
00
11 00 00
00
SDO client
SDO server
(CAN-8123/CAN-8223/
CAN-8423)
scs
: 2
n
: 3
e
: 1
s
: 1
m
: 01 10 00
d
: 11 00 00 00
Step 7. Users can send the data to RxPDO1 with data length 2. Then, the
EMCY message containing the error reset information will be received.
Because the value of TxPDO is the same with the previous one, the DO
channels will not change.
11-bit COB-ID (bit)
Func Code
Node ID
8-byte Data (byte)
10 9 8 7 6 5 4 3 2 1 0
RTR
Data
Length
0
1
2
3 4 5 6 7
0 1 0 0 0 0 0 0 0 0 1
0
2
00 00 00
00
00 00 00
00
PDO
consumer
PDO producer
(CAN-8123/CAN-8223/
CAN-8423)
COB-ID
: 0x201
L
: 2
PDO-msg
: 00 00 00 00 00 00 00 00