CAN-8123/CAN-8223/CAN-8423 user’s manual (Revision 3.00, May/22/2009) ------
168
information. When interpreting these objects, the ASCII table will be needed.
5. The range of the 0x100c is from 0 to 32767 in CAN-8123/CAN-8223/CAN-8423. For more
information of the object with index 0x100C and 0x100D, please refer to the section
5.4.2.
6. For the object with index 0x1014, please refer to the section 5.3.1.
7. The object with index 0x1015 stores the inhibit time period between two EMCY message.
The function of this object is similar to the PDO communication object with sub-index 04.
It is valid for avoiding the large loading on the CAN bus when transmitting a lot of EMCY
messages. This parameter range is from 0 to 32767 for the
CAN-8123/CAN-8223/CAN-8423, and the unit of EMCY inhibit time is ms.
SDO Communication Entries
Idx Sidx
Description
Type
Attr
Default
1200h
0h largest sub-index supported for
“server SDO parameter”
UNSIGNED 8
RO
2
1h COB-ID form client to server
(RxSDO)
UNSIGNED 32
RO
600h+Node-ID
2h COB-ID form server to client
(TxSDO)
UNSIGNED 32
RO
580h+Node-ID
RxPDO Communication Entries
Idx Sidx
Description
Type
Attr
Default
1400h
0h largest sub-index supported for
“receive PDO parameter”
UNSIGNED 8
RO
2
1h
COB-ID used by PDO (Rx)
UNSIGNED 32
RW
200h+Node-ID
2h
transmission type
UNSIGNED 8
RW
FFh
1401h
0h largest sub-index supported for
“receive PDO parameter”
UNSIGNED 8
RO
5
1h
COB-ID used by PDO (Rx)
UNSIGNED 32
RW
300h+Node-ID
2h
transmission type
UNSIGNED 8
RW
FFh
1402h
0h largest sub-index supported for
“receive PDO parameter”
UNSIGNED 8
RO
5