CAN-8123/CAN-8223/CAN-8423 user’s manual (Revision 3.00, May/22/2009) ------
143
Bit Meaning
0 generic
error
1 current
2 voltage
3 temperature
4
communication error (overrun, error state)
5
device profile specific
6
reserved (always 0)
7 manufacturer
specific
The emergency error codes and the error register are specified in the
following table.
Emergency
Error Code
Manufacturer Specific Error
Field
High
Byte
Low
Byte
Error
Register
First Two
Byte
Last Three
Byte
Description
00
00
00
00
00
00 00 00
Error Reset or No Error
10
00
81
01
00
00 00 00
CAN Controller Error Occur
50
00
81
02
00
00 00 00
EEPROM Access Error
50
00
81
03
00
00 00 00
COM Port Access Error
81
10
11
04
00
00 00 00
Soft Rx Buffer Overrun
81
10
11
05
00
00 00 00
Soft Tx Buffer Overrun
81
10
11
06
00
00 00 00
CAN Controller Overrun
81
30
11
07
00
00 00 00
Lift Guarding Fails
81
40
11
08
00
00 00 00
Recover from bus off
82
10
11
09
00
00 00 00
PDO Data length Error
FF
00
80
0A
00
00 00 00
Request to reset Node or
communication
After producing the EMCY message, the emergency object data will be saved
to the object with index 0x1003, and the error register of the emergency object
data will be mapped to object 0x1001. Therefore, users can use these two
objects to view what happened in the CAN-8123/CAN-8223/CAN-8423 and
check the error history.