CAN-8123/CAN-8223/CAN-8423 user’s manual (Revision 3.00, May/22/2009) ------
193
I-8017HS/I-8017HW
Analog Input Type Definition
Back to table
Range Code
(Hex)
Output Range
Data Format
Max Value
Min Value
Input Range
+10.000 V
-10.000 V
0
(default)
-10 to 10V
Hexadecimal 1FFF
2000
Input Range
+5.000 V
-5.000 V
1
-5 to 5V
Hexadecimal 1FFF
2000
Input Range
+2.500 V
-2.5000 V
2
-2.5V to +2.5V
Hexadecimal 1FFF
2000
Input Range
+1.250 V
-1.250 V
3
-1.25V to +1.25V
Hexadecimal 1FFF
2000
Input Range
+20.000 mA -20.000 mA
4
-20 mA to +20 mA
Hexadecimal 1FFF
2000
I-8080/ 8084W
Counter Input Type Definition
Back to table
Range Code
(Hex)
Counter Type
Channel
number
Max Value
Min Value
2147483647
-2147483648
0
*1
Dir/Pulse
Counter 4
1FFFFFFF 80000000
2147483647
-2147483648
1
*1
Up/Down
Counter 4
1FFFFFFF 80000000
-
-
2 Frequency 8
- -
4294967295
0
3
(default)
Up Counter
8
FFFFFFFF 00000000
2147483647
-2147483648
4
*1
(for I-8084W)
AB Phase
4
1FFFFFFF 80000000
Note:
*1: The sub-index of all parameters and input channels are still 8, but the sub-index 1 is
equal to sub-index 2, and sub-index 3 is equal to sub-index 4, and so on.