CAN-8123/CAN-8223/CAN-8423 user’s manual (Revision 3.00, May/22/2009) ------
178
6.4 Object of Counter/Frequency Modules
(Only for I-8080 and I-8084W)
Idx S-idx
Description
Type
Attr PDO
mapping
Default
3000h 0h largest sub-index supported for
“read counter / frequency 32-bit”
UNSIGNED 8
RO
No
---
1h
Read counter / frequency with ch1
UNSIGNED 32
RO
Yes
---
...
...
...
...
...
3001h 0h largest sub-index supported for
“read counter overflow 16-bit”
UNSIGNED 8
RO
No
---
1h
Read counter overflow with ch1
UNSIGNED 16
RO
Yes
---
...
...
...
...
---
3002h 0h largest sub-index supported for
“reset counter value with writing 0”
UNSIGNED 8
RO
No
---
1h
Reset ch1 counter value
UNSIGNED 8
WO
Yes
---
...
...
...
...
---
3003h
0h
largest sub-index supported for “set
XorRegister with 0 or 1”
UNSIGNED 8
RO
No
---
1h
XorRegister value of ch1 UNSIGNED
8
RW
No
---
...
...
...
...
---
3004h
0h
largest sub-index supported for “set
frequency mode with 0, 1, or 2”
UNSIGNED 8
RO
No
---
1h
Frequency mode of ch1
UNSIGNED 8
RW
No
---
...
...
...
...
---
3005h
0h
largest sub-index supported for “set
frequency update time (unit – ms)”
UNSIGNED 8
RO
No
---
1h
Frequency update time of ch1
UNSIGNED 16
RW
No
---
...
...
...
...
---
3006h 0h largest sub-index supported for
“enable/disable low pass filter”
UNSIGNED 8
RO
No
---
1h
Low pass filter status of ch1
UNSIGNED 8
RW
No
---
...
...
...
...
---
3007h
0h
largest sub-index supported for “set
low pass filter time (unit - us)”
UNSIGNED 8
RO
No
---
1h
Low pass filter time of ch1
UNSIGNED 16
RW
No
---
...
...
...
...
---