I-7550E PROFIBUS/Ethernet Converter User Manual
(Version 1.00, June/2014)
PAGE: 88
(2)
ERROR MSG INFO
:
The user can check Error message in this page as shown in
Figure
95
. The I-7550E will log some errors that are not affect
communication. It will help the user to find out the issue of data
communication. Most of Error message are about Output header
format because I-7550E will follow Output header to send data. And
sometimes the wrong setting of output header doesn’t affect
communication. Below is the Error message list and description:
Message
Description
Output length is zero
The Byte 10 of output header is
zero. Data won’t be sent.
Output length is too large
The Byte 10 of output header is
over PROFIBUS output IO
length when the Byte 8 is 1.
Total length Error!
The total length(Byte 5~6) is
over 1460
Target ID is error!
The Byte 7 is error value.
Total Num Index Error!
The Byte 8 is zero.(this value
should be 1 At least
Total/Current length diff!
The total length(Byte 5~6) is
different from Byte 10 when the
Byte 8 is 1.
Combine Header connectionID
diff!
All of combined output data
should be the same setting value
of output header.
Combine Header MsgID diff!
Total length combined data is
different from the length of data
that I-7550E received.
Combine Header Index error!
Combine Header Index error!
Combine Total Length error!
Combine Data 1st index error!
The index setting of the first
combined data is error value.