I-7550E PROFIBUS/Ethernet Converter User Manual
(Version 1.00, June/2014)
PAGE: 31
Table 15 The value of output area of “System setting module”
Module
Byte
Data type
Representation
Value
System setting
module
Output 0
Byte
Hex
0x01
Output 1
Byte
Hex
0x00→ 0x01
Output 2
Byte
Hex
0x00
Output 3
Byte
Hex
0x07
Output 4
Word
Hex
0x00
Output 6
Word
Hex
0x14
Output 8
Byte
Hex
0x01
Output 9
Byte
Hex
0x00
Output 10
Byte
Hex
0x14
3.4.2 Output data with Combine Method
The I-7550E provides “Combined Method” that can combine the data from
PROFIBUS Master and sends to Ethernet device at once.
In this example, we assume the I-7550E is configured output data length as 220
Bytes, and the user wants to send 300 Bytes package to Ethernet device with
connection ID 11. The PROFIBUS Master needs to send 2 packages to the I-
7550E, and these 2 output data of “System setting module” are as shown
Table
16
and
Table 17
.
It is very import that Byte 3
、
Byte 4
、
Byte 6
、
Byte 8 must be the same in 2
package header. If there are different in these values, the I-7550E will ignore
these data and sends diagnostic message to the PROFIBUS Master.
Table 16 The value of output area for 1
st
package
Module
Byte
Data type
Representation
Value
System setting
module
Output 0
Byte
Hex
0x01
Output 1
Byte
Hex
0x00→ 0x01
Output 2
Byte
Hex
0x00
Output 3
Byte
Hex
0x0B
Output 4
Word
Hex
0x01
Output 6
Word
Hex
0x12C
Output 8
Byte
Hex
0x02
Output 9
Byte
Hex
0x00
Output 10
Byte
Hex
0xDC