I-7550E PROFIBUS/Ethernet Converter User Manual
(Version 1.00, June/2014)
PAGE: 64
Check “UDP Server Enable” and set UDP Port as 1000.
In Allow IP address field, set S_IP1 as 192.168.253.1, “Timout “
values as 0 and “Protocol Type” as 1. Check “S-IP1” in Enable
Connection IP field.
Figure 64 Set the configuration of UDP server
Press “Save to Device” to save settings to EEPROM of I-7550E and
restart I-7550E. The user can power on I-7550E again or press
“Reboot” button to restart the I-7550E.
Figure 65 Press “Save to Device” to save settings to the I-7550E, and restart the
I-7550E.