I-7550E PROFIBUS/Ethernet Converter User Manual
(Version 1.00, June/2014)
PAGE: 20
During the Combined Method, if a data received from PROFIBUS Master Device
is not correct combined method package, the I-7550E will clear previous
combined method packages and diagnostic message will be sent to PROFIBUS
Master as shown
Figure 17
.
Ethernet Device
P
R
O
F
IB
U
S
Byte 0
Byte 239
.
.
.
.
.
.
.
.
.
New Data,
Not
combined
package
Circular
Byte 19
System
setting
module
Output Data
(Max:240 Bytes)
1
st
Package
2
nd
Package
3
rd
Package
Circular
PROFIBUS FIFO
Clear Previous
Packages
New Data
Figure 17 Receive new data during Combined Method
3.2 Ethernet Protocol
The I-7550E has below features for Ethernet:
●
Maximum length of data is up to 1460 Bytes
●
Can be as TCP/UDP server.
●
Can be as TCP/UDP client.
●
Maximum 8 allowing clients when the I-7550E is as server
●
Maximum 8 targeting servers when the I-7550E is as client.
The I-7550E provides Web Configuration for the user to configure the settings of
TCP/UDP via browser (Please refer to section 5.2).
The I-7550E supports TCP and UDP protocol and it can be as Server or Client.
When the I-7550E is TCP/UDP server, it allows the maximum 8 connections from
client devices. Also the I-7550E can be as TCP/UDP client and it can connect with
the maximum 8 target server devices as shown
Figure 18
.