I-7550E PROFIBUS/Ethernet Converter User Manual
(Version 1.00, June/2014)
PAGE: 57
--Set the I-7550E in Read/Write mode.
The user need to set the I-7550E in Read/Write mode(Please refer to section
3.3.1). We set Byte 0 of system setting module as 0x01 as shown
Figure 54
Figure 54 Set Byte 0 of system setting module as 0x01to let the I-7550E in
Read/Write mode.
-- Set the output data area of “System setting module”.
Now we need to set other the necessary value in the output data are of “system
setting module” and “Output module” for sending data to TCPServer as shown
Table 25
、
Table 26 and Figure 55.
Table 25 The value of output area of “System setting module”
Module
Byte
Data type
Representation
Value
System setting
module
Output 0
Byte
Hex
0x01
Output 1
Byte
Hex
0x00→ 0x01
Output 2
Byte
Hex
0x00
Output 3
Byte
Hex
0x09
Output 4
Word
Hex
0x00
Output 6
Word
Hex
0x0A
Output 8
Byte
Hex
0x01
Output 9
Byte
Hex
0x00
Output 10
Byte
Hex
0x0A
Table 26 The value of “Output module”
Module
Byte
Data type
Representation
Value