The number of stations in a PROFIBUS network is restricted to 126. According
to the PROFIBUS specification up to 32 stations are allowed per segment. A
repeater has to be used to link the bus segments.
2.4 Setting the PROFIBUS Address
The station address of I-7550E can be set by using either the DIP switch or by
writing it directly to the EEPROM. The DIP switch covers a range from 0 to 255.
The valid address range of a PROFIBUS station spans from 0 to 126.
Table 6
shows three examples of setting the station address by using the DIP switch. The
DIP switches are accessed by opening the modules housing (
Figure 8
)
.
Table 7
explains which address will be used by the module after power on, if the DIP
switch address setting differs from the address stored in the EEPROM.
Table 6 DIP switch setting example
Station address
DIP switch (SW1)
1
2
3
4
5
6
7
8
1
1
0
0
0
0
0
0
0
10
0
1
0
1
0
0
0
0
126
0
1
1
1
1
1
1
0
Note: 1=>ON, 0=>OFF
Table 7 The Address setting of the I-7550E
DIP switch Setting
Description
0~125
1.
The address setting of the EEPROM is ignored.
2.
The address cannot be set by the PROFIBUS configuration
tool.
126-254
1.
The address setting of the DIP switch is ignored.
2.
If the address in the EEPROM is 126, the PROFIBUS
configuration tool can set a new address and save it to the
EEPROM.
255
1.
Slave address in the EEPROM is set to 126.