I-7550E PROFIBUS/Ethernet Converter User Manual
(Version 1.00, June/2014)
PAGE: 40
“Input Data Error”. The diagnostic messages are shown in
Table 21
.
Table 21 Diagnostic messages
Messages
Description
Note
Connection ID error
(0x01-0x11)
Disconnected(0x01)
Receive Data Error(0x02)
System setting module
Error(0x82)
Not find System setting module.(0x3D)
Position is not correct!(0x3E)
Output Data Error
(0x83)
Output Header Error(0x3A)
Trigger Byte Error!(0x3B)
FIFO overflow(0x3E)
Data lose.(0x3F)
Input Data Error
(0x85)
FIFO overflow (0x60)
Data lose.(0x63)
PS:
Diagnostic message will also be shown in input data area of System setting
module (Please refer to section 3.3.2)
a. When the I-7550E receives a “data output command” (output byte 1) from
system setting module, and this command didn’t increase in order (ex: 0->1, 1-
>2,…, 255->0), the I-7550E will think that it lose some output data of the
PROFIBUS Master and a diagnostic message (“Trigger Byte Error”) will be sent
by the I-7550E to the PROFIBUS Master.
b. When the FIFO is overflow, it means that the users send data from Ethernet to
I-7550E fast. The user should adjust the timing of sending data.
c.
When the user set the wrong value of output data area of “System setting
nodule”, it may not affect the communication but the I-7550E will send a
diagnostic message to the PROFIBUS Master. Meanwhile, the user can check
more detail error message by browser the web of the I-7550E. The user can
check it on website “Information”->”ERROR_MSG_INFO”(Please refer to
section 5.3, “F. Information”).
4.5 Establish connection with I-7550E
Before establishing a connection between the DP-Master and the I-7550E, user