System Location
Style AWG
# of wires
Watertight Plug
Watertight Receptacle
FC 8991
World Trade
(200-415 VAC)
single-phase / 14 ft.
Type DP-1
#10 AWG
3 wire
(not provided - see Note
2)
(not specified - see Note
2)
FC 8998
World Trade
(200-480 VAC)
three-phase / 14 ft.
Type LSZH
#10 AWG
4 wire
(not provided - see Note
2)
(not specified - see Note
2)
FC 8999
World Trade
(200-415 VAC)
single-phase / 14 ft.
Type LSZH
#10 AWG
3 wire
(not provided - see Note
2)
(not specified - see Note
2)
IBM continues to strongly recommend the use of a metal backbox (example shown below)
with our line cords using IEC-309 plugs.
Although in-line connectors and nonmetallic backboxes are available and compatible, they
are not recommended. These recommendations are based on the metal backbox providing:
Notes:
1. An added level of protection against a mis-wired phase and ground reversal.
2. In some cases, a metal backbox may be better for EMI mitigation.
You may choose not to use a metal backbox. In this case, please check your local code for
specific requirements.
Notes:
1. The customer must obtain the appropriate plugs and receptacles, based on existing
electrical codes, where those plugs and receptacles are not provided with the system.
These customer-provided plugs and receptacles should be installed by qualified
electricians.
2. The power cord set(s) provided are for use only with this product.
3. LSZH = low smoke, zero halogen
Wire colors for cut-end cords
Wire Number
Color
Description
Line 1
Brown
Phase 1 (labeled "PH-1" on the wire insulation
Line 2
Black
Phase 2 (labeled "PH-2" on the wire insulation
Line 3
Gray
Phase 3 (labeled "PH-3" on the wire insulation
Ground
Green/Yellow
Ground (labeled "GND" on the wire insulation
Drain
clear or uninsulated
Cable shield - must be connected to GROUND
Level 03c, May 2011
48
z10 BC IMPP
|
||||
|||
|||
|||
|||
|||
Содержание Z10 BUISNESS CLASS Z10 BC
Страница 1: ...System z10 Business Class Installation Manual for Physical Planning GC28 6875 03 Level 03c May 2011...
Страница 2: ......
Страница 3: ...System z10 Business Class Installation Manual for Physical Planning GC28 6875 03 Level 03c May 2011...
Страница 8: ...Level 03c May 2011 vi z10 BC IMPP...
Страница 10: ...Level 03c May 2011 viii z10 BC IMPP...
Страница 44: ...Level 03c May 2011 32 z10 BC IMPP...
Страница 50: ...Level 03c May 2011 38 z10 BC IMPP...
Страница 62: ...Level 03c May 2011 50 z10 BC IMPP...
Страница 86: ...LC Duplex Connectors ISC 3 Links ISC 3 Links FC 18 02 ISC 3 Level 03c May 2011 74 z10 BC IMPP...
Страница 106: ...Level 03c May 2011 94 z10 BC IMPP...
Страница 110: ...Level 03c May 2011 98 z10 BC IMPP...
Страница 112: ...Level 03c May 2011 100 z10 BC IMPP...
Страница 116: ...Level 03c May 2011 104 z10 BC IMPP...
Страница 130: ...Level 03c May 2011 118 z10 BC IMPP...
Страница 131: ......
Страница 132: ...Level 03c May 2011 Printed in USA GC28 6875 03...