Example 3 (single distribution panel)
In this example, the computer receives power from two separate circuit breakers in
a single power panel. This does not make use of the redundancy provided by the
processor. It is, however, acceptable if a second power distribution panel is not
available.
This type of power distribution will result in system outage in the event of a power
failure at either the switch gear or the distribution panel.
Switch Gear
Distribution
Panel
System
z10
System
z10
Level 03c, May 2011
Dual power installation
103